In the market, we often hear batteries with nominal capacities of 100Ah, 150Ah, 200Ah, etc. How do you get the capacity here? Do batteries with the same nominal capacity have the same actual lead-acid battery capacity?
1. What is actual capacity and rated capacity?
- Actual capacity
Under the conditions of specified discharge rate, discharge end voltage and temperature, the power output by a lead-acid battery or battery pack is expressed in ampere hours (Ah), with the symbol Ca and a indicating the number of hours.
The symbol Ia represents the discharge current. Due to the chemical reaction characteristics of the battery, the relationship between the discharge time T (hours) and the capacity of the lead-acid battery is nonlinear. Ca=Ia*T
- Rating capacity
When the I10 discharge current is specified, the discharge end voltage is 1.8V (the rated voltage of the battery cell is 2V, the 12V battery has 6 cells, the end voltage is relative to 1.8*6) and the temperature is 25℃±5℃, the battery output The power is C10.
- Other discharge time standards:
- C10: 10-hour rated capacity, discharge end voltage 1.8V, value 1.00C10, unit ampere-hour (Ah);
- C3: 3-hour rated capacity, discharge termination voltage 1.7V, value 0.75C10, unit ampere-hour (Ah);
- C1: 1 hour rate rated capacity, discharge termination voltage 1.6V, value 0.55C10, unit ampere-hour (Ah);
- I10: 10 hour rate discharge current, value is 0.1C10, unit is Ampere (A);
- I3: 3 hour rate discharge current, value is 0.25C10, unit is Ampere (A);
- I1: 1 hour rate discharge current, value is 0.55C10, unit is Ampere (A);
2. The main components of the positive plate and negative plate of lead-acid batteries
The main active material of the positive plate is lead dioxide, while the main active material of the negative plate is lead sponge.
3. Why do lead-acid batteries generate heat when charging?
During the charging process of the battery, part of the electrical energy is converted into chemical energy, and the other part is converted into heat energy and other energy.
It is normal to generate heat during battery charging, but if the temperature is too high, you should promptly check whether the charging current is too large or whether there is a short circuit inside the battery. Here are more about bms for lead acid battery.
The relationship between calorific value and electrolyte volume is small. For example, if the battery is a sealed battery and the amount of electrolyte is small, the internal resistance of the battery will increase, resulting in heat generation and a higher terminal voltage during charging, which will further affect the capacity of the lead-acid battery.
4. Basic knowledge of lead-acid battery capacity
Lead-acid battery capacity refers to the amount of electricity released by the battery under specific conditions. It can be divided into theoretical capacity, actual capacity and rated capacity. In actual engineering applications, only the rated capacity and actual lead-acid battery capacity are concerned.
Rated capacity refers to the lead-acid battery capacity under rated conditions (temperature, discharge duration, discharge termination voltage, etc., such as 25 ℃, constant current discharge duration of 50 h, 20 h, 10 h or 5 h, termination voltage of 1.85 V, etc. )
 The minimum amount of electricity Q that must be discharged, recorded as CN. Domestic lead-acid batteries generally use a capacity with a constant current discharge time of 10 h (called a 10 h discharge rate) as the rated capacity, which is recorded as C10. Rated capacity can be understood as the maximum available capacity under rated conditions.
The actual capacity refers to the amount of electricity that the battery can output when it is discharged to a certain end voltage under conditions different from the rated conditions. It is also called the available capacity and is recorded as Cd. During constant current discharge, the actual capacity is equal to the product of the discharge current I and the discharge time t, that is, Cd = It.
If you are also interested in lithium batteries, please click lead acid battery vs lithium ion for comparison information of the two batteries.
The remaining capacity refers to the remaining capacity of the lead-acid battery that can be output when the battery actually releases a certain amount of electricity but is not fully discharged, recorded as Cr. When the battery is discharged to the end voltage under non-rated conditions, the remaining capacity = rated capacity – available capacity, that is, Cr = CN – Cd.
5. How to calculate lead-acid battery capacity?
The popular HOXIE calculation method or ladder calculation method for lead-acid battery capacity is derived from the conversion coefficient. In the literature Some discharge characteristics of lead acid batteries, HOXIE obtained the ladder calculation method based on the following method: the entire discharge time is divided into 2 time periods.
When the load gradually decreases, the remaining capacity calculation method is greater than the capacity obtained by the ladder calculation method; when the load gradually increases, the remaining capacity calculation method is smaller than the capacity obtained by the ladder calculation method.Â
However, the physical meaning of the remaining capacity calculation method is clearer, and the calculation results are closer to the actual demand capacity.Â
At the same time, the remaining capacity calculation method only uses one capacity conversion coefficient at each stage, which greatly simplifies the process of calculating lead-acid battery capacity compared with the traditional ladder calculation method.
In recent years, in response to the shortcomings of the traditional ladder calculation method, some other solution methods have emerged, such as the lead-acid battery capacity calculation method for power DC power supply systems based on capacity decomposition (referred to as the basic capacity method).
In the basic capacity method, lead-acid battery capacity is divided into basic capacity and consumption capacity. The basic capacity is the basic capacity to maintain constant current discharge under the discharge termination voltage, recorded as CB.
It is generally the capacity required for the initial discharge of the battery for 5 seconds, which can be obtained from the capacity conversion coefficient; the consumption capacity is the capacity used for load consumption during constant current discharge, denoted as CU.
The greater the current, the greater the CB; if the current decreases, CB releases part of the capacity accordingly and converts it into consumed capacity for the load. The released capacity is recorded as CF.
The basic capacity method has clear physical meaning and does not need to calculate the maximum capacity value in stages. However, when the discharge current changes stepwise, the basic capacity method needs to compare the consumed capacity Cu in the subsequent stages with the released partial capacity CF.
Therefore, the steps of comparing the capacity in stages by the traditional ladder calculation method are advanced to the basic capacity for calculation. Here are more about bess manufacturers.Â