energy storage system

Grid-connected vs. stand-alone energy storage technologies, what are the differences?

Grid-connected vs. stand-alone energy storage technologies, what are the differences
Currently, there are two types of energy storage PCS control technologies: network type and network type. The grid-following type is essentially a current source and cannot provide voltage and frequency support by itself. It must rely on the voltage and frequency of the grid and cannot support the system.
Table of Contents
    Add a header to begin generating the table of contents

    The grid-connected type is essentially a voltage source. It internally sets voltage parameter signals to output voltage and frequency, and can be connected to the grid. It can also be operated off-grid and has strong support for the power grid in global energy storage.

    YouTube_play_button_icon_(2013–2017)

    1. The essence of network-based energy storage

    Networked energy storage is essentially one of the energy storage technologies and a voltage source with internal resistance and controlled amplitude and phase.

    The voltage source determines the amplitude through reactive power control, and uses different control methods to control the phase depending on whether there is a constant voltage source on the DC side of the PCS. If there is a constant voltage source on the DC side of the PCS (such as a constant power flexible DC converter station, etc.), the voltage phase is determined by active power control;

    If there is no constant voltage source on the DC side of the PCS (such as a constant DC voltage flexible DC converter station, etc.) ), the network PCS itself is required to control its DC voltage, and the voltage phase is determined by the DC voltage control.

    2.PCS control strategy

    Based on the two major control schemes of active power and DC voltage, the networked PCS synchronous control architecture can be further subdivided according to the characteristics of the controller. Active power synchronous control can be divided into droop control, virtual synchronous generator control, virtual oscillator control and power synchronous control, etc. DC voltage synchronous control can be divided into matching control, etc.

    Here are more information about balcony solar storage system.

    Research on grid-connected energy storage technology is more matur

    3. Networking PCS function

    • Build grid voltage

    The network-type PCS can achieve the same functions as the synchronous generator in terms of operating mechanism and characteristics through the synchronous generator ontology model (VSG). Here are more about bess manufacturing company.

    VSG simulates the frequency and voltage regulation process of synchronous generators, simulates the excitation regulation process of synchronous generators with reactive power-voltage control, provides active inertia support, restores the output characteristics of synchronous generators, and achieves network construction capabilities.

    • Frequency modulation and inertia response

    When a disturbance occurs in the power system, the parameters such as the moment of inertia J and damping coefficient D controlled by the VSG slow down the change of the system frequency, which helps to improve the stability of the frequency and power angle, because the moment of inertia J in the VSG does not really exist.

    The amount can be flexibly set without hardware restrictions. At the same time, the network-type PCS has a 1.2 times instantaneous overload capability and can better support inertia response.

    • Suppression of broadband oscillations

    On the one hand, the network-type PCS can reduce the risk of low-frequency oscillation through flexible damping D. On the other hand, it can achieve impedance reshaping and oscillation suppression at characteristic frequencies by introducing virtual impedance, edge damping and other solutions.

    • Voltage fault ride-through

    When the grid is under-crossed, the grid-type PCS will perform limiting control and overload virtual impedance control to ensure that the PCS can operate as a voltage source to participate in grid construction during a fault; when the grid is under-cut, the grid-type PCS will add the terminal voltage in real time Control voltage regulation to suppress grid voltage overcharging and participate in grid construction with fast reactive power response. Click here get more about Top 10 high capacity battery cell.

    • black boot

    The network-type PCS has the ability to start and support the restart after the system crashes. It can complete the establishment of AC voltage by itself, provide the required excitation for the main power generation unit, and can also set up the power grid by itself when necessary.

    However, due to the large current impact at the black start moment, A single device cannot drive the auxiliary load, so the EMS needs to schedule multiple networked PCSs to start in parallel to support the transformer to establish excitation and complete voltage establishment.

    Grid-connected energy storage is a voltage source

    4. Comparison between network type and network type energy storage PCS

    Control method

    • Network PCS

    It mainly controls the AC current measurement, tracks the existing grid voltage phase angle through a phase-locked loop, and then forms a control signal after coordinate transformation and PWM modulation and feeds it back to the switching tube.

    Advantages: The control structure is simple, and the phase-locked loop technology is relatively mature at this stage, so the system can be controlled under the condition that the system determines the current and maximum power point.

    Disadvantages: Although the phase-locked loop technology that the control relies on is relatively mature, it still needs to passively obtain the stable frequency and voltage reference values provided by the power grid to work properly, and the stability of its own control loop is weaker than that of the network-type energy storage loop, so it cannot Acts as an active support system.

    • Network PCS

    Different from the grid-based control that uses phase-locked loops to synchronize the power grid, the grid-based PCS sets the voltage reference signal internally and synchronizes with the rest of the grid after passing through the power calculation module and frequency droop control. Similar to synchronous generator control, no external voltage reference signal is relied upon.

    Advantages: It has the ability to mobilize its own operation and adjust the output in real time when there is no external power supply. It maintains the voltage output through power output adjustment, forms a voltage source connected to the grid, and maintains system stability. In addition, it can form an independent power grid in a weak power grid without a rigid voltage source. Grid.

    Disadvantages: The overcurrent capacity of the mesh type PCS is increased from 1.5 times to 3.0 times, so the cost is significantly higher than that of the mesh type.

    Application scenarios

    • Environment with weak power grid

    Although the phase-locked loop control method used in grid-type PCS is mature in technology, it is prone to strong coupling with the reactance in the power grid in an environment where the power grid is relatively weak, causing problems for the stability of new power systems with a large proportion of power electronic devices.

    It has a greater impact and is less likely to be coupled with the energy storage device. The grid-type PCS has voltage source characteristics and uses a power synchronization control strategy to directly adjust and synchronize the active/reactive power when the output of the power generation side fluctuates. Compared with the phase-locked loop, the grid frequency and its output phase need to be measured to achieve control. Synchronization is more efficient and flexible.

    In summary, since the network-based PCS abandons the phase-locked loop control mode, it is more suitable for use in weak power grid environments.

    • Island mode

    The mesh-type PCS needs to use an external rigid AC system as a reference value for frequency and voltage to achieve control synchronization, so it cannot operate in island mode. Due to its power synchronization control characteristics, the networked PCS can perform power control synchronization on its own without relying on externally transmitted phase information, so it can work in both islanding and grid-connected modes.

    In summary, since the network-based PCS does not rely on external information transmission, it is suitable for the island mode.

    Environment with strong power grid

    Network-following PCS uses phase-locked loops to extract frequency phases, which is more direct and effective. At the same time, the cost of network-based PCS is relatively high at this stage, so network-following PCS is more suitable for strong power grid environments.

    Grid-connected PCS can reduce the risk of low-frequency oscillation